Fix Cold Steam Heating Radiators & ConvectorsHow to diagnose & fix a too-cold steam radiator?
What to check first. Troubleshooting cold steam radiators: this article describes the diagnosis & repair of cold steam heating convectors or steam radiators.
We also describe how to fix a steam radiator that is too hot and we include warnings about other radiator or baseboard types that are too hot or that overheat.
And we list less common causes of cold steam radiators in buildings and we describe how to fix these conditions.
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?
First let's be sure we're reading the best cold-radiator diagnostic advice for your situation.
This article will help you fix a steam heating system radiator that is not heating up as it should.
If your heating system uses steam radiators or steam convectors then you are on the right page to get help in diagnosing and fixing steam radiators that won't get hot. Continue reading below.
If your heating system runs on hot water (it's a hydronic heating system) but it uses those skinny horizontal baseboards instead of radiators, you will be happier if you
see BASEBOARD HEAT REPAIR for cold baseboard diagnosis and repair.
Our page top heating system illustration and the sketch at left were provided compliments of Carson Dunlop Associates, a Toronto home inspection, education & report writing tool company [ carsondunlop.com ].
Make sure that your room thermostat is set to a temperature higher than the temperature in the room - so that it is calling for heat.
Make sure that your heating boiler is working, that is that the heating boiler turns on and off normally. A steam boiler will usually turn on right away in response to the thermostat being turned up or on a call for heat.
Make sure that the control valve at the heating radiator is "open" or "on" as we describe just below.
First check the radiator valve itself.
At COLD HEATING RADIATOR REPAIR (hot water / hydronic heat) we illustrated different types of heating radiator control valves and explained their operation.
Details are at RADIATOR VALVES & HEAT CONTROLS.
It's standard to ask first "is the radiator valve turned on or "open" (fully counter-clockwise)?
Experts warn that a radiator slow to heat could have a supply valve that is too small (the problem would always have been observed since date of installation) or a supply valve that is partly closed (the problem would have originated when the valve was closed and would go away when the valve is fully opened, provided the valve is undamaged and really opens internally when its handle is turned.)
We also see both radiators and other forms of steam or hot water heat that are not hot enough if the supply piping is undersized, a valve is partly closed, piping is clogged or blocked, or the hot water flow rate or for steam heat the rise of steam is too slow.
Other problems can cause a steam heat radiator to stay cold when you want heat as we explain next where after the above digression we continue our diagnostic and repair advice for cold radiators or convectors in steam heating systems.
If some of your steam heat radiators are not getting hot,
the steam vent may not be working, may not be venting at all (radiator stays cold) or may be venting too slowly (radiator heats to proper temperature but too slowly)[2]
If a steam radiator valve is open but the radiator is still cold, the steam vent may not be working.
Our photo at left shows a typical steam radiator vent.
When steam is first rising in the heating system, the steam heating radiator will be cool as will be the steam vent. The vent opens, allowing rising steam to enter the radiator by pushing air out through the vent.
When the steam radiator and steam vent are warm or hot, the vent closes. If a steam vent stops working, rising steam cannot enter the radiator and it will be slow to heat or may not heat at all.
See STEAM VENTS and
also STEAM HEATING SYSTEMS for details about the choice, installation, diagnosis & repair of steam radiator vents - a common source of cold steam radiators, slow to heat steam radiators, even overheating steam radiators and that incessant hissssssss or spitting condensate when a steam vent doesn't close as it should.
A cold upper part of the radiator may indicate the
vent is plugged with scale or is malfunctioning.
Vapor or slight moisture from the vent is normal.
Steam continuously passing through the vent
indicates a malfunction. Replace the vent as
needed or every 10 years.
Source: ITT Hoffman Specialty STEAM VENTS for RADIATORS MODEL 1A 1B AIR VALVE INSTALLATION INSTRUCTIONS [PDF] (2007), ITT 8200 N. Austin Ave. Morton Grove, IL 60053 tel: 847-966-3700 fax: 847-966-9052 www.hoffmanspecialty.com
If there are no steam vents on your steam heat radiators don't despair: your steam heat is probably a two-pipe steam heating system that uses
STEAM TRAPS - take a look at that article: steam traps are used on two pipe steam heating systems to release air and condensate while keeping hot steam in the radiator.
Steam radiator sloped the wrong way - steam condensate blockage
As our Carson Dunlop Associates sketch shows (above, left), steam radiators can be sensitive to exactly how they are installed and pitched or sloped.
You'll want to learn if your steam heating system is a "one pipe" or a "two pipe" design, but in either case, if the steam supply or condensate return piping have been moved or settled so as to have lost the proper slope, correcting those conditions may be needed.
That's because condensate, produced by cooling steam in the radiator, has to be able to drain back out of the radiator.
A steam radiator that is sloped the wrong way, perhaps due to building floor settlement or a change made by an inexperienced re modeler, will become partly or even completely blocked by accumulated condensate, leading to loss of heat.
Steam heating system controls, inspection, diagnosis, and repair
are discussed beginning
Above: dust-clogged fins on the tubing in a heating convector unit block air flow and so reduce its heat output. Vacuum ff the dust carefully to avoid bending the fins.
If your steam radiator is too hot in a two-pipe steam system, according to the U.S. DOE, check the steam traps:
In two-pipe systems, older steam traps often stick in either the open or closed position, throwing off the balance in the system.
If you seem to have problems with some radiators providing too much heat and others providing too little, this might be the cause.
The best approach is often to simply replace all the steam traps in the system.
If your electric heater is too hot or is not shutting off when you think it should
see ELECTRIC BASEBOARD HEAT INSPECTION
Watch out: an overheating electric heater is a fire hazard.
Also see HEAT WON'T TURN OFF for complete diagnosis of too much heat or heat that won't turn off.
I did learn how to fix a steam boiler who as cold radiator !! That was great !! thanks to inspectApedia webside (Nov 17, 2015) Anonymous
Thank you for the nice feed-back. We work hard to provide useful information so are really happy when it works out well for our readers. We also welcome criticism, content suggestions, questions: working together makes us smarter.
...
...
Continue reading at RADIATOR STEAM VENTS or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.
Or see these
STEAM HEAT RADIATOR REPAIR at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.
Or see this
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
Questions & answers or comments about how to troubleshoot cold steam radiators, baseboards, or convector heaters.
Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.
Search the InspectApedia website
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.
In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com
We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.
In addition to any citations in the article above, a full list is available on request.