InspectAPedia®   -   Search InspectApedia

 a heating boiler circulator pump setHeating System Circulator Pumps & Circulator Relays
- home


Circulator pump sources, circulator pump installation & repair manuals

Hot water heating circulators or circulator pumps: install, troubleshoot, repair advice: this article series discusses Circulator Pumps: how to find, inspect, diagnose, and repair problems with Hot Water Heating System Circulator Pumps or circulator pump relay switches and controls.

This article series answers most questions about Heating System Boiler Controls on central heating systems to aid in troubleshooting, inspection, diagnosis, and repairs.

Circulator pump relay switches & controls on heating systems: Troubleshooting & Repair Guide, How to tell if a heating circulator pump is working, Why do some heating zones work and others not, why does heat come out of zones where thermostats are not calling for heat?

How to fix an air-bound heating system and blocked circulator pump,

How to cure circulator pump noises, Where should a circulator pump be installed on a heating boiler? On the inlet or on the outlet side of the boiler? Use of air exit tanks and circulator pumps on heating boilers.

InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.

- Daniel Friedman, Publisher/Editor/Author - See WHO ARE WE?

Install, Dagnose & Fix Heating Circulator Pumps

B&G Red Circulator Pump (C) Daniel Friedman

Heating circulator pumps or "zone circulators" are used to force hot water from the heating boiler through radianting devices such as hot water baseboards or radiators. The circulator is switched on as needed or in some designs may be wired to run continuously.

Our photo above of a red B&G heating circulator pump shows equipment more than twenty years old and still spinning along nicely.

Proper installation, protection from leaks, and lubrication at annual service can give a long circulator life. Poor maintenance or improper installation can give less happy results.

After a brief introduction we describe what goes wrong (or how to get things to go right with heating zone circulator pumps.

We also link to related articles for circulator choices, installation, troubleshooting, repair or replacement.

Also see CIRCULATOR OPERATION CHECKS

How Hot Water Heating Circulators Work: One vs Multiple Circulators

Multiple heating zones with individual circulators (C) Daniel Friedman

Hot water may be circulated throughout multiple zones using a single circulator pump and individual zone flow control valves, or each heating zone may be built with its own individual circulator pump.

Either approach to individual heating zone control can work just fine - using zone valves or using individual circulators.

Our photo above shows a single circulator system (no zone valves are in the photo - this may be a single-zone heat system) while at left our photograph shows a three-zone heating system with three B&G circulators in a home in Two Harbors, MN.

You'll notice that one of the circulators has been replaced with a newer Bell & Gossett Circulator SLC-30.

See MULTIPLE HEATING ZONE CONTROL for as much argument as you can stand about multiple circulator pumps versus multiple zone valves for heating zone control.

See HOT WATER HEAT SUB-ZONE CONTROLS - circulators or zone valves - for a description of splitting up an existing heating zone into individually-controlled sub-zones.

What goes wrong with hot water heating circulator pumps and circulator switches?

Leaky circulator pump (C) Daniel Friedman

The heating system circulator pump, such as the trio of pumps shown at the top of this page, is used to move hot water from the heating boiler out through one or more loops of piping in a building, through heating devices such as radiators, heating baseboards, or convector units, then through return piping back to the heating boiler.

When the water temperature drops to a pre-set level the heating boiler will re-heat the water.

[Click to enlarge any image]

The circulator relay is an electrical switch which, in response to a request for heat from a thermostat, turns on the circulator pump.

See RELAY CONTROL SWITCHES for details about how the circulator pump relay operates.

Single Circulator Heating Systems, One or Multiple Heating Zones

Some heating systems use a single circulator to move hot water through the building's heating devices (convectors, radiators or baseboards).

In a one-circulator system, the building may still divide its heat into various zones or sub-areas of individual heat control, by using either individual radiators in rooms or perhaps by using electrically controlled zone valves which open and close flow of hot water through sub-loops in the building heating piping.

Also see ZONE VALVES, HEATING - home.

Even a single zone heating system might use two circulator pumps. In this case the second circulator is being used to control a separate indirect-fired water heating system to provide domestic hot water for washing and bathing.

See INDIRECT FIRED WATER HEATERS.

Multiple Circulator Heating Systems, Multiple Heating Zones

Some heating systems use multiple circulators to provide heat to individual building areas or "zones".

In this case each heating zone will have its own thermostat which, acting as a low-voltage "heat on-off switch" will turn on individual circulator pumps when heat is desired in that zone.

Details are

at CIRCULATOR PUMP RELAYS & OTHER CONTROLS.

Also see RELAY CONTROL SWITCHES for details about how circulator relay controls work.

Mixed Multiple Circulator Heating Systems Plus Zone Valves

Less common are mixed heating zone systems in which multiple circulators are used but one or more of the circulators feeds a heating water pipe which is subsequently divided into additional sub-zones of heat control, each sub-zone being controlled by a zone valve.

We often see this arrangement when the building owner/manager wants to sub-divide an existing heating zone into multiple zones of control.

Circulator pump leak at mounting flange (C) Daniel Friedman

Before assuming the heating system is not working when the thermostat is calling for heat, feel the radiators or baseboards to see if they are getting hot.

On a call for heat at the thermostat, if the heating boiler is already hot (above the lower limit or cut-in temperature) then the circulator should turn on and move hot water to the baseboards or radiators.

Only after the boiler temperature drops below the cut-in temperature will the heating boiler turn on to re-heat the water. The connection between the thermostat and the heating boiler turning on or off is indirect.

On most heating systems the thermostat turns the circulator pump on or off and the temperature of the heating water turns the heating boiler on or off.

Our photo (above left) shows leaks at the circulator pump mounting flanges. Notice those rust stains on the bottom circulator mounting flange.

See CIRCULATOR PUMP LEAKS

Circulator pump mount (C) Daniel Friedman


If the boiler runs but the heating baseboard or radiators in an area do not get hot, the problem could be

Honeywell room thermostat

If the heating boiler itself if does not turn on in a response to a call for heat 

see NO HEAT - BOILER.

Circulator Pump Failure or Noise Diagnostic Checklist

Ambrol BoilerMate WH-7P circulator pump issues (C) InspectApedia.com Randall SmithWhat causes repeated failure of circulator pump on tankless water heater?

Another reader asked:

We had a circulator on our indirect HW heater die (loud noises) and replaced. This had initial problems due to air in the pipes, but once fixed there was little/no hot water and within a day the new circulator died as well.

Plumber suggested a control value that is supposed to control flow was broken and opened it fully, noting this would make the hot water very hot (adults only in house) and would need to be fixed properly soon.

Now, however, we are hearing the new circulator struggle with loud humming noises. Any ideas? Many thanks! - 2019/01/23 Randall Smith said:

Reply: some diagnostic checkpoints for noisy or failed circulator pumps: Causes & Effects

Randall

Thanks for an interesting and also of course troubling question. One can but suspect that we have not gotten down to the root cause of the problem.

It would be helpful to have

It's not clear to me how an anti-scald valve (I think that's the device your plumber calls a control valve) would cause circulator pump failure. Hydronic heating circulator pumps are designed to handle boiler water at the temperatures that occur normally in the heating system - up to close to 200 degF.

Obvious & Subtle Causes of Heating or Hot Water Circulator Pump Failure

...

Circulator pump company contact information & installation & repair manuals

  • Also see AIR-BOUND HEATING SYSTEMS for diagnosis and repair steps
  • Also see CIRCULATOR PUMP RELAY MANUALS
  • Armstrong ARMSTRONG ASTRO CIRCULATOR PUMP MANUAL [PDF] Armstrong Fluid Technology,

    Excerpt: Armstrong Astro 2 circulators are designed for closed hydronic or potable water systems. Their intended use is for circulating water or glycol solutions. For pumping domestic water use non-ferrous lead free bronze or stainless steel body pump construction.

    Toronto 23 bertrand avenue toronto, ontario canada m1l 2p3 +1 416 755 2291

    Buffalo 93 east avenue north tonawanda, new york u.s.a. 14120-6594 +1 716 693 8813

    Birmingham heywood wharf, mucklow hill halesowen, west midlands united kingdom b62 8dj +44 (0) 8444 145 145

    Manchester wolverton street manchester united kingdom m11 2et +44 (0) 8444 145 145

    Bangalore #59, first floor, 3rd main margosa road, malleswaram bangalore, india 560 003 +91 (0) 80 4906 3555

    Shanghai no. 1619 hu hang road, xi du township feng xian district, shanghai p.r.c. 201401 +86 21 3756 6696

    São Paulo rua josé semião rodrigues agostinho, 1370 galpão 6 embu das artes sao paulo, brazil +55 11 4781 5500
  • Bell & Gossett Air Separators and other heating system components, 8200 N. Austin Ave., Morton Grove IL 60053, USA - Tel 847 966-3700 Fax 847 965-8379 . Air separators are discussed by B&G at http://www.bellgossett.com/homeowners/BG-airseparator.asp
  • B&G: "Instruction Manual, Bell & Gossett Series LR Circulators" P86101D, Mayu 2012, Xylem Inc. 8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/bellgossett

    See BELL & GOSSETT B&G EQUIPMENT MANUALS & CONTACT for our complete collection of B&G circulator manuals
  • Also see BOILER CONTROLS & SWITCHES
  • Also see BOILER CONTROLS: MANUALS for HEATING SYSTEMS
  • Grundfos, Poul Due Jensens Vej 7 DK-8850 Bjerringbro, Denmark Tel.: +45 87501400 retrieved 2020/04/15, original source: https://www.grundfos.com/service-support/encyclopedia-search/air-vent.html

    GRUNDFOS Kansas City 17100 West 118th Terrace Olathe, Kansas 66061 USA Phone: (913) 227-3400 www.grundfos.us

    GRUNDFOS Canada 2941 Brighton Road Oakville, Ontario L6H 6C9 Canada Phone: +1-905 829 9533 www.grundfos.ca

    GRUNDFOS México Boulevard TLC No. 15 Parque Industrial Stiva Aeropuerto C.P. 66600 Apodaca, N.L. México Phone: 011-52-81-8144 4000 Fax: 011-52-81-8144 4010 www.grundfos.mx

    GRUNDFOS ALPHA SERIES VARIABLE SPEED CIRCULATOR PUMP INSTALLATION [PDF] Grundfos Pumps Corporation 17100 W. 118th Terrace Olathe, Kansas 66061 Telephone: (913) 227-3400 Fax: (913) 227-3500

    GRUNDFOS UP SERIES CIRCULATOR PUMPS INSTALLATION GUIDE
    [PDF]
    Excerpts:

    Closed systems Model UP(S) 15, 26, 43 and 50 series pumps with cast iron pump housings are designed to pump water compatible with their cast iron construction. They are recommended for use in closed hydronic systems (i.e. airless, non- potable water).

    Open systems Model UP(S) 15, 26, 43 and 50 series pumps with stainless steel or bronze pump housings are designed to pump water compatible with their construction and can be used in both open and closed systems.


    Grundfos UPS15-58 and UP15-42F CIRCULATOR INSTALLATION INSTRUCTIONS [PDF]

    GRUNDFOS UP(S) 15 HOT WATER CIRCULATING PUMP MANUAL
    [PDF] (2014) used on recirculating domestic hot water systems

    GRUNDFOS UP(S) 15 HOT WATER CIRCULATING PUMP MANUAL
    [PDF] (2011) used on recirculating domestic hot water systems

    VENTING AIR from HEATING SYSTEMS [PDF] Grundfos, , sources of air in hydronic heating systems and methods for getting rid of it (and why we care)

    Grundfos offers this source of circulator pump manuals: https://www.grundfos.com/grundfos-for-engineers/project-assistance-search-page/how-to-find-installation-and-operation-manuals-online.html
  • Honeywell Sparco AMX circulators air purgers, air scoops, and other heating system components & controls,

    Honeywell International Inc. 1985 Douglas Drive North Golden Valley, MN 55422 USA

    Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Toronto, Ontario M1V 4Z9 Canada Email: customer.honeywell.com

    See HONEYWELL CONTROLS On HVAC Equipment, thermostats, primary controls, zone valves - for our complete list of Honeywell controls & manuals

    HONEYWELL AMX Series DirectConnect MANUAL [PDF] (2010) Any application requiring accurate control of water temperature based on mixing of hot and cold water,
  • Raypak, Installation and Operation Instructions, Raytherm Residential Boilers [PDF] courtesy of Raypak®, and technical advisor Wayne Hoffman, personal communication 5/11/2009. Mr. Hoffman is a technical advisor with more than 30 years experience in the heating field. r


    Raypak is a Rheem company that provides hydronic heating boilers for residential, pool, and commercial use. Raypak can be contacted at 866-583-0664 for technical support or for assistance in selecting the proper heating equipment for a specific application. Rheem Corporation is a manufacturer of water heaters and heating equipment including Ruud heating and cooling products.

    Websites: http://www.raypak.com and http://www.rheem.com/
  • Taco circulators, air scoops and other heating system components & controls: Taco Inc., 1160 Cranston Street, Cranston, RI 02920 / (401) 942-8000 / Fax (401) 942-2360 Taco (Canada) Ltd., 6180 Ordan Drive, Mississauga, Ontario L5T 2B3 / (905) 564-9422 / Fax (905) 564-9436 www.taco-hvac.com

    See details and manuals found at TACO DIAGRAMS, MANUALS, PARTS, CONTACT TACO components & controls

    Taco also has some helpful FAQs that are useful in diagnosing circulator problems - see http://www.taco-hvac.com/en/faq.html#
  • Also see Circulator Pump Relays cited at RELAY CONTROL SWITCHES
  • WATTS HOT WATER CIRCULATOR DIAGNOSTIC MANUAL [PDF] Watts Premier, Inc., Phoenix, AZ 85027 Phone: 800-752-5582 www.wattspremier.com

...




ADVERTISEMENT





Reader Comments, Questions & Answers About The Article Above

Below you will find questions and answers previously posted on this page at its page bottom reader comment box.

Reader Q&A - also see RECOMMENDED ARTICLES & FAQs

Lochinvar sidewall fan/powered vent cap must be interlocked with the control

My daughter and son-in-law have a Lochinvar CBN-135M9 boiler system with 4 zone controls. It also has the flow switch wired to the outdoor temp sensor input. According to the installation manual it should be wired to an ignition delay circuit to keep it from firing if the circulator isn't running.

It was apparently installed that way initially (2014) and has been heating since then, tho one upstairs circuit is very difficult to bleed the air out of.

They had an HVAC guy come out to clean and inspect, and he left the wiring as-is. This strikes me as possibly dangerous--the ignition lockout is disabled, and the temp sensor is seeing a dead short across it.

Should we be worried about this weird arrangement?

Could the short across the temp inputs be holding the pressure down to account for the bleed difficulty? On 2020-11-03 by zapster

by (mod) - Lochinvar CBN-135M9 boiler system also has the flow switch wired to the outdoor temp sensor input

If I understand the wiring question properly this quote from a typical Lochinvar manual may be useful:

The sidewall fan/powered vent cap MUST be interlocked with the units control system to start the fan on a call for heat and prove fan operation before the boiler fires.

Watch out: However rather than speculate and with the apology that I just don't know enough about the system you're discussing to have a confident opinion that it is safe or unsafe, why don't you give the boiler manufacturer a call and ask them directly. That would be the most authoritative source.

See the contact information as well as a list of boiler manuals found

at LOCHINVAR HEATING BOILERS or call their Technical support: 800-722-2101


Radiant heat floor circulator pump heard running when heat is OFF

I have infloor heat and in May turn the heat off but often I hear the circulator going . It is eaten by electric On 2020-04-29 by Anonymous

by (mod) - look for a stuck circulator relay or bad switch

Anon:

Depending on where you live, your heating system may have been set up so that the circulator runs continuously, with the room thermostat's turning the boiler on and off as needed on a call for heat. That's how hot water (hydronic) heating systems are usually installed in Canada.

In the U.S., more-often the thermostat turns the circulator on and off and the water temperature turns the boiler's burner on and off as needed.

So if yours is an "always-on" installation then you'll want to find the separate electrical power switch for the circulator(s) and flip it off - taking care to remember to turn in back on at the start of heating season.

If yours is NOT a "circulator always-on" system, then I would look for shorted thermostat wires or a stuck circulator relay that needs repair or replacement.

Thanks for asking a helpful question. Let me know what your service tech finds.

by Anonymous

thank you so much for your response, I guess I was not very clear, I am in Canada, I have turned the fuse for the heater off but every once in a while (not constantly) the circulator will come on,

so if I understand you correctly there is a separate switch for the circulator? I am a widow whose husband looked after all this and I am sorry to sound so ignorant.

Reply by (mod) -

Yes there will be a separate circulator switch. Follow the wires


Diagnose noisy "struggling" circulator pump

12 yr. old Amtrol indirect-fired water heater's 3d circulation pump is failing, extremely noisy and struggling.

Tank is still fine, apparently-- way past warranty of course.

Amazing actually that any pump could survive, handling that rusty sludge from cast-iron steam pipes! Anybody know if its longevity is typical? About to have it replaced-- On 2020-03-07 by KT

by (mod) - short hot water circulator life on an indirect-fired water heater system

KT

This is certainly a troublesome problem report: short hot water circulator life on an indirect-fired water heater system.

I agree that steam heat boilers often produce a lot of scale as well as rust and crud - which is why the steam controls like the boiler Low Water Cutoff need to be flushed monthly.

So we're circulating silty steam boiler water from the steam boiler's water reservoir through the heat exchanger in the indirect water heater. And you report that's killing the circulator pumps.

I would discuss with your service tech

1. do we need to go through a more-aggressive cleanout flush of the steam boiler?

2. do we need to use a water conditioner or treatment additive in the steam boiler to reduce the rust and scale problem?

(those are good for the boiler and heating system as well)

3. should we install a large particle filter in the indirect water heater line from the boiler ahead of the circulator pump?

4. Should we be installing a scale-tolerant circulator pump? Grundfos, Taco, Liang and Watts all make circulator pumps that can tolerate some scale in the heating water.


New B&G Ecocirc 19-16 CCFXYZ TEmperature reduced from 200F to 190F

Amtrol WH-series indirect water heater piping details (Recommended) with separate circulator, adapted from Amtrol BoilerMate(TM) IO Manual cited in detail at InspectApedia.com (C) IAP 2019Thanks for the help! I've attached one image (can't seem to figure out how to do multiples) that shows the circulator, the water heater, and the pipes connecting them.

The new circulator is a B&G Ecocirc 19-16 CCFXYZ. The other (older) circulators for the house heat are by Taco, model 007-F4.

The water heater, if it matters, is an Amtrol 'Boiler Mate' WH-7P (41 gallons).

The operating temperature at the boiler is set at 190 now, had been 220. When doing the initial repair the plumber felt the ~200F+ & ~20psi was too high and reduced it to 190F max and 15psi.

Not sure if this is related to our current problems. On 2019-01-23 by Randall Smith -

by (mod) - troubleshooting indirect water heater circulator pump failures

Yep, Clark Van Oyen's comments box code only permits one image per comment, but of course one can post multiple comments (and images at one per).

220F is too hot for a normal boiler and risks dumping at the TP Relief valve.

The best aquastat settings would be HI 200, LO 20 or more below the HI,

I might keep the DIFF circuit working and set DIFF to the max or 25. to keep heat in the boiler to speed response when the indirect heater ("zone") wants help from the boiler.

The indirect water heater runs as what looks to the boiler and aquastat as simply another heating zone.

Amtrol warns against scalding hazards and recommends a tempering valve.

If you give us the brand and model of your tempering valve we can be sure we've found the installation instructions and proper positioning information.

The sketch above is adapted from the Amtrol BoilerMate™ WH-series INSTALLATION MANUAL [PDF] (2012) AMTROL, 1400 Division Road, West Warwick, RI 02893 T: 401.884.6300 F: 401.885.2567 www.amtrol.com

 

Watch out: Radiator exploded after circulator pump repair

I have a boiler for heat in my home with two circulator pumps that supply two different zones (upstairs and downstairs).

My circulator pump for the first floor went bad and was replaced, fixing the problem. The boiler itself had no issues.

An hour later, a radiator upstairs (different zone supplied by the other circulator pump) exploded and a 6 inch piece of metal was cast from the radiator causing water to flood the house.

This happened in a different zone connected to the other pump from the same boiler.

Could the exploded radiator in the other zone have been affected by the replacement of the circulator pump to the other zone?

I cant understand how this coincidentally happened when there seemed to be no problems with the supply to the zone on the second floor where it happened. Any feedback is appreciated. (Jan 30, 2014) Heather

Reply:

Heather,

This sounds horrible - and peculiar. Forensic investigators start by disbelieving coincidences.

But it's not clear why a radiator would explode under any circumstances. Really "explode" ? We're talking about hot water heat, at normal pressures under 30 PSI.

Watch out: if your heating system pressures were abnormally high (over 30 psi) then either your system was missing a critical safety device - a Temperature/pressure relief valve at the boiler - or the valve was installed but was jammed, or subverted, or not working.

IF that is is the case this is a VERY DANGEROUS condition as an exploding boiler can cause a BLEVE explosion of tremendous force. (Search InspectAPedia for Bleve explosion to read Details).

In short, a normal hot water heating circulator pump does not have great pumping power; if there was an overpressure problem in the system it seems more likely it came from another component. Naturally everbody involved in working on your system will be scared to admit fault. Focus on a thorough inspection of the heating boiler starting with

- the location, type and condition of pressure/temperature relief valve
- the normal operating pressure and temperature of the boiler

If on your own, before the heating company shows up, if you see high pressure readings on the boiler gauge (30 psi or above) or if you see water spilling out of a relief valve I would SHUT OFF THE SYSTEM immediately and would get the heck out of there.

Follow-up:

The PSI was not high before the repair. It was around 12. After the repair and the flooding upstairs, it is running around 18 psi now. I did look at the system this morning.

The only problem I see is that a pressure reducing valve has a slow drip from the bottom. The valve for the intake had been turned off last night to stem the flooding and then turned back on after the flow to that radiator was capped so I don't know if that affected the valve since it is about 10 inches away from the cutoff.

Reply:

12 PSI cold is normal for a typical 2 story home.

BTW I would not want to confuse an air bound system with one that is at too low pressure.

 

What's the cost to replace a heating circulator pump?

How much should it cost to replace a circulator pump in a single family rowhome? I have a 9 yr old Bryant boiler. Not sure of the make or BTU. Thanks On 2014-11-05 by Mary

Reply by (mod) -

Mary depending on brand and model a new hydronic heating system (hot water) circulating pump costs between about $140. and $350. U.S. plus labo.

The labor cost will vary depending on where you live and on how much trouble it is to get to the equipment, and on details such as whether or not service valves are already installed on either side of the circulator since if there are none the technician will probably have to drain and refill the heating sytstem - adding time and cost.

Circulator pump cost

See CIRCULATOR PUMP REPAIR FAQs

Circulator mounting position vs system pressure

See CIRCULATOR PUMP REPAIR FAQs

How to Hook Up Multiple Circulators or Zones

We moved this discussion to a new article: please see MULTIPLE HEATING ZONE CONTROL

Circulator pump won't start

We moved this discussion to a new article: please see CIRCULATOR WONT RUN

Circulator pump runs intermittently

We moved this discussion to a new article: please see CIRCULATOR PUMP RUNS INTERMITTENTLY

Weak Heat Questions

We have moved this discussion to a new article: please see WEAK HEAT, WEAK CIRCULATOR, TOO COOL

Circulator Pump Noises, heating system noises

We have moved this discussion to a new article: please see CIRCULATOR PUMP NOISES.

Also see HEATING SYSTEM NOISE DIAGNOSIS for a more broad range of heating noise diagnosis & repair procedures.

Circulator pump runs even when we are not asking for heat

See CIRCULATOR PUMP REPAIR FAQs

 

Thank you to our readers for their generous comments

Good tutorial - On 2011-10-21 by construction

...

Continue reading at BYPASS a BAD CIRCULATOR or select a topic from the closely-related articles below, or see the complete ARTICLE INDEX.

Or see CIRCULATOR PUMP REPAIR FAQs - questions & answers posted originally on this page - for diagnostic questions & answers about heating circulator pumps & circulator relays

Or see these

Recommended Articles

Suggested citation for this web page

CIRCULATOR PUMPS & RELAYS at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair, & problem prevention advice.


Or see this

INDEX to RELATED ARTICLES: ARTICLE INDEX to HEATING BOILERS

Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia

Ask a Question or Search InspectApedia

Try the search box just below, or if you prefer, post a question or comment in the Comments box below and we will respond promptly.

Search the InspectApedia website

Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.

Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification
when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.


Comment Form is loading comments...

 

IF above you see "Comment Form is loading comments..." then COMMENT BOX - countable.ca / bawkbox.com IS NOT WORKING.

In any case you are welcome to send an email directly to us at InspectApedia.com at editor@inspectApedia.com

We'll reply to you directly. Please help us help you by noting, in your email, the URL of the InspectApedia page where you wanted to comment.

Citations & References

In addition to any citations in the article above, a full list is available on request.

  • "Residential Hydronic (circulating hot water) Heating Systems", Instructional Technologies Institute, Inc., 145 "D" Grassy Plain St., Bethel, CT 06801 800/227-1663 [home inspection training material] 1987
  • Heating, Ventilating, and Air Conditioning Volume I, Heating Fundamentals,
  • Boilers, Boiler Conversions, James E. Brumbaugh, ISBN 0-672-23389-4 (v. 1) Volume II, Oil, Gas, and Coal Burners, Controls, Ducts, Piping, Valves, James E. Brumbaugh, ISBN 0-672-23390-7 (v. 2) Volume III, Radiant Heating, Water Heaters, Ventilation, Air Conditioning, Heat Pumps, Air Cleaners, James E. Brumbaugh, ISBN 0-672-23383-5 (v. 3) or ISBN 0-672-23380-0 (set) Special Sales Director, Macmillan Publishing Co., 866 Third Ave., New York, NY 10022. Macmillan Publishing Co., NY
  • Installation Guide #200 for Residential Hydronic Heating Systems, The Hydronics Institute, 35 Russo Place, Berkeley Heights, NJ 07922
  • In addition to citations & references found in this article, see the research citations given at the end of the related articles found at our suggested

    CONTINUE READING or RECOMMENDED ARTICLES.


ADVERTISEMENT