Description
Issue overview
Minimum Exhaust Flow Fraction Schedule Name in ZoneHVAC:ExhaustControl seems to be not 1 but 0 by default, which results in no exhaust air flow when this field is left blank.
See the UnmetHours link for details.
Operating System (Multiple choices)
Any
Operating System Version
Any
Version of EnergyPlus
25.1.0
Unmethours link or helpdesk ticket number
https://unmethours.com/question/102547/zonehvacexhaustcontrol-does-not-work/