One unit can support these DHW configurations: (1) single-pass with a swing tank, (2) single-pass return-to-primary (no swing tank), and (3) multi-pass. The unit must be set up to match the piping configuration used.
Return-to-primary means the building recirculation loop returns to the primary storage tank rather than a swing tank. This can reduce system complexity compared to a swing-tank approach. Follow the manual’s piping details for valves, strainers, and sensor placement.
Yes. Velo is fully ductable on both intake and discharge. Duct design must account for service access and allowable static pressure.
Not always. Velo can run in return-to-primary configurations that do not use a swing tank. Some designs still use a swing tank, depending on project goals and layout.
For ductless intake, Velo can be installed directly side-by-side with no side clearance requirement. Optional side clearance can make some maintenance tasks easier.
Yes. Velo includes an integral circulator. The submittal lists design flows, pressure drops, and external head allowance by mode.
Common options include a BMS Gateway, a main control panel for staging multiple units, and a remote outdoor sensor for interior ducted applications.
Yes, outdoor installation is supported. Cold-climate installs require proper piping protection, freeze protection planning, and power planning per the installation manual.
Velo can support recirculation in multiple system configurations, including return-to-primary setups. Use the manual’s piping guidance for recirc pump placement and minimum flow expectations.
The ambient operating range is 10°F to 120°F.
Maximum service water temperature is 160°F.
Nominal DOE capacity is 180,000 BTU/hr. AHRI 1160 capacity is 157,000 BTU/hr at the listed AHRI test conditions.
Nominal DOE performance is 4.1 COP. AHRI 1160 performance is 3.2 COP at the listed AHRI test conditions.
Performance varies by ambient temperature. The submittal includes capacity and COP data down to 10°F for both heat-recovery (single-pass demand) and multi-pass demand modes.
Velo uses R513A refrigerant. (Why not CO2? Learn the little-known truth here.)
Velo is available in 208–230V 3-phase 60Hz or 460V 3-phase 60Hz. Electrical values (MCA/MOCP) vary by power package. Control power is 120V single-phase 60Hz.
The standard power approach supports freeze protection power needs and service design. The Unified Power Package option consolidates feeds into a single-point power configuration. Use the submittal option list when specifying.
Domestic water connections are 1-1/2 in FPT. Condensate connection is 1 in.
The easiest way to size a system is request a selction from the Nyle applications team. Responses are quick and thorourgh.



By submitting this form, you agree to our Terms and Conditions and Privacy Policy.
By submitting this form, you agree to our Terms and Conditions and Privacy Policy.
By submitting this form, you agree to our Terms and Conditions and Privacy Policy, and occasional email correspondence from Nyle. You can unsubscribe at any time.

By submitting this form, you agree to our Terms and Conditions and Privacy Policy.

By submitting this form, you agree to our Terms and Conditions and Privacy Policy.

By submitting this form, you agree to our Terms and Conditions and Privacy Policy.

By submitting this form, you agree to our Terms and Conditions and Privacy Policy.

By submitting this form, you agree to our Terms and Conditions and Privacy Policy.