Describe the bug
For PV-battery configurations with DC-connected batteries, with transformer losses specified, SAM calculates very large loss values.

A workaround is to assign the transformer loss input to the AC wiring loss category and set transformer loss inputs to zero.
https://sam.nrel.gov/forum/forum-general/3700
To Reproduce
Steps to reproduce the behavior:
- Create a default PV-Battery / Single Owner case.
- On the Losses page set both the transformer load and no load loss values to 0.2%.
- On the Battery Cell and System page, choose the DC Connected option.
- Run.
Expected behavior
Annual transformer loss percentage in results should be of similar magnitude as input percentages.
Operating System and Version
SAM 2021.12.02, tested in Windows
Describe the bug
For PV-battery configurations with DC-connected batteries, with transformer losses specified, SAM calculates very large loss values.
A workaround is to assign the transformer loss input to the AC wiring loss category and set transformer loss inputs to zero.
https://sam.nrel.gov/forum/forum-general/3700
To Reproduce
Steps to reproduce the behavior:
Expected behavior
Annual transformer loss percentage in results should be of similar magnitude as input percentages.
Operating System and Version
SAM 2021.12.02, tested in Windows