Incorrect cycling calculation for HeatPump:PlantLoop:EIR:*objects #11202

@lymereJ

Description

@lymereJ

Issue overview

The defect file includes a HeatPump:PlantLoop:EIR:Heating which is setup with a reference COP of 1.0 and with no capacity and EIR degradation (curves output = 1). It has a minimum PLR of 0.5. I would expect to see that below the minimum part load ratio that the compressor would cycle proportionally to the load, however, it does not appear to be the case, see the figure below.

Image

Operating System (Multiple choices)

MacOS

Operating System Version

15.6.1

Version of EnergyPlus

25.1 and lastest develop

Unmethours link or helpdesk ticket number

N/A

Defect file

large_office_vav_hw_reheat_const_spd_awhp.txt